Introduction
Isolation Handcart is a popular selection of vacuum circuit breaker parts. Our TAG2 indoor assembly poles type isolation handcart is the latest domestic achievement. It is suitable for Air-insulated Switchgear (Ampower-KYN28A, ABB-Unigear, Siemens-Nxair, Schneider-Nvnex and so on) and able to be interchanged with similar products. And it is available in many varieties, excellent in performance, and widely applicable to:
1. Energy and infrastructure: power plants, 220KV/110KV substations, primary and secondary distribution systems.
2. Industrial production: power supply systems for pulp and paper, construction materials (glass, cement, ceramics), steel and metal products, aluminum, petrochemical and other industrial productions.
3. Building: power supply system of large, medium-sized buildings and residential areas.
4. Other: petrochemical, transportation, and mining areas.
Standard Compliance
IEC 62271-100
|
High Voltage AC Circuit Breakers
|
IEC 60694
|
Common Specification for High Voltage Switchgear and Control Gear Standards
|
GB1984-2003
|
High Voltage AC Circuit Breakers
|
GB/T11022-1999
|
Common Technical Requirements for HV Switchgear
|
DL/T 402-1999
|
Technical Specification for HV AC Circuit Breaker
|
DL/T 403-2000
|
Technical Specification for12kV- 40.5kV indoor HV AC Circuit Breaker
|
DL/T 593-2006
|
Common Specification for HV Switchgear Enquiry and Orders
|
JB/T 3855-1996
|
Technical Specification for 3.6kV- 40.5kV indoor HV AC Circuit Breaker
|
Complete Series
Mounting way: Withdrawable type(7.2kV-24kV), Floor type(40.5kV)
CB Truck drive way: Manual, Electric
Rated voltage: 6kV(7.2kV), 10kV (12kV), 15kV(17.5kV), 20kV (24kV), 36kV (40.5kV)
Rated current: 630A, 1250A,1600A, 2000A, 2500A, 3150A,4000A,
Technical Parameters
Rated voltage
|
Ur [kV]
|
7.2/12/17.5
|
24
|
40.5
|
Rated insulation voltage
|
Us [kV]
|
7.2/12/17.5
|
24
|
40.5
|
Power frequency withstand voltage
|
Ud (1min)[kV]
|
25/42/45
|
79
|
95
|
Lightning impulse withstand voltage
|
Up [kV]
|
60/75/95
|
145
|
185
|
Rated frequency
|
Fr [Hz]
|
50/60
|
50/60
|
50/60
|
Rated current
|
Ir [A]
|
630, 1250
|
630, 1250
|
630,1250, 1600,2000, 2500,3150, 4000
|
1250, 1600, 2000,2500, 3150, 4000
|
630, 1250
|
630, 1250
|
630, 1250, 1600,2000, 2500,3150
|
630, 1250
|
630, 1250
|
630, 1250, 1600,2000, 2500,3150
|
Rated breaking capacity
|
Isc [kA]
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
Rated short time withstand current
(4 seconds)
|
Ik [kA]
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
Closing capacity
|
Ip [kA]
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
Order of operations
|
[O-0.3s-CO-15s-CO]
[O-0.3s-CO-180s-CO]
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
[O-180s-CO-180s-CO]
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
─
|
Opening time
|
[ms]
|
─
|
─
|
─
|
Arcing time
|
[ms]
|
─
|
─
|
─
|
Breaking time
|
[ms]
|
─
|
─
|
─
|
Closing operation rated voltage
|
[V]
|
─
|
─
|
─
|
Opening operation rated voltage
|
[V]
|
─
|
─
|
─
|
Charging motor rated voltage
|
[V]
|
─
|
─
|
─
|
Charging motor rated power
|
[W]
|
─
|
─
|
─
|
─
|
─
|
─
|
Energy storage time
|
[s]
|
─
|
─
|
─
|
Mechanical endurance
|
[ cycles ]
|
─
|
─
|
─
|
Auxiliary switch
|
NO+NC
|
─
|
─
|
─
|
Secondary circuit power frequency withstand voltage (1min)
|
[V]
|
2,000
|
2,000
|
2,000
|
Short circuit current breaking times
|
[ cycles ]
|
─
|
─
|
─
|
Rated short time current duration
|
[s]
|
─
|
─
|
─
|
Breaker grading
|
[ms]
|
─
|
─
|
─
|
More details please go to "Download" area to download the catalogs or contact us!
|