Introduction
Vacuum circuit breaker (VCB) is an electrical switch designed to protect electrical circuits from damage caused by overload or short circuit. Our TAV1 indoor embedded poles type vacuum circuit breaker (VCB) is the latest domestic achievement. It is suitable for Air-insulated Switchgear (Ampower-KYN28A, ABB-Unigear, Siemens-Nxair, Schneider-Nvnex and so on) and able to be interchanged with similar products. And it is available in many varieties, excellent in performance, and widely applicable to:
1. Energy and infrastructure: power plants, 220KV/110KV substations, primary and secondary distribution systems.
2. Industrial production: power supply systems for pulp and paper, construction materials (glass, cement, ceramics), steel and metal products, aluminum, petrochemical and other industrial productions.
3. Building: power supply system of large, medium-sized buildings and residential areas.
4. Other: petrochemical, transportation, and mining areas.
Standard Compliance
IEC 62271-100
|
High Voltage AC Circuit Breakers
|
IEC 60694
|
Common Specification for High Voltage Switchgear and Control Gear Standards
|
GB1984-2003
|
High Voltage AC Circuit Breakers
|
GB/T11022-1999
|
Common Technical Requirements for HV Switchgear
|
DL/T 402-1999
|
Technical Specification for HV AC Circuit Breaker
|
DL/T 403-2000
|
Technical Specification for12kV- 40.5kV indoor HV AC Circuit Breaker
|
DL/T 593-2006
|
Common Specification for HV Switchgear Enquiry and Orders
|
JB/T 3855-1996
|
Technical Specification for 3.6kV- 40.5kV indoor HV AC Circuit Breaker
|
Complete Series
Mounting way: Fixed type, Withdrawable type, Side mounting type, Floor type(40.5kV)
CB Truck drive way: Manual, Electric
Rated voltage: 6kV(7.2kV), 10kV (12kV), 15kV(17.5kV), 20kV (24kV), 36kV (40.5kV)
Rated current: 630A, 1250A,1600A, 2000A, 2500A, 3150A,4000A,
Rated short circuit breaking current: 20kA, 25kA, 31.5kA, 40kA
Technology Leader
TAV1 series indoor medium voltage embedded poles type vacuum circuit breaker are used the world latest embedded poles, the embedded pole is based on epoxy resin and cast by the most advanced APG technology. Vacuum interrupter, primary conductive circuit parts and isolated rod are enclosed together in the embedded pole to achieve a complete separation between the conductive circuit and the exterior. The structure is miniaturized and maintenance free, while having high dielectric strength, so as to allow the vacuum circuit breaker to run normally in harsh environment.
Technical Parameters
Rated voltage
|
Ur [kV]
|
7.2/12/17.5
|
24
|
40.5
|
Rated insulation voltage
|
Us [kV]
|
7.2/12/17.5
|
24
|
40.5
|
Power frequency withstand voltage
|
Ud (1min)[kV]
|
25/42/45
|
79
|
95
|
Lightning impulse withstand voltage
|
Up [kV]
|
60/75/95
|
145
|
185
|
Rated frequency
|
Fr [Hz]
|
50/60
|
50/60
|
50/60
|
Rated current
|
Ir [A]
|
630, 1250
|
630, 1250
|
630,1250, 1600,2000, 2500,3150, 4000
|
1250, 1600, 2000,2500, 3150, 4000
|
630, 1250
|
630, 1250
|
630, 1250, 1600,2000, 2500,3150
|
630, 1250
|
630, 1250
|
630, 1250, 1600,2000, 2500,3150
|
Rated breaking capacity
|
Isc [kA]
|
20
|
25
|
31.5
|
40
|
20
|
25
|
31.5
|
20
|
25
|
31.5
|
Rated short time withstand current
(4 seconds)
|
Ik [kA]
|
20
|
25
|
31.5
|
40
|
20
|
25
|
31.5
|
20
|
25
|
31.5
|
Closing capacity
|
Ip [kA]
|
50
|
63
|
80
|
100
|
50
|
63
|
80
|
50
|
63
|
80
|
Order of operations
|
[O-0.3s-CO-15s-CO]
[O-0.3s-CO-180s-CO]
|
■
|
■
|
■
|
─
|
■
|
■
|
■
|
■
|
■
|
■
|
[O-180s-CO-180s-CO]
|
─
|
─
|
─
|
■
|
─
|
─
|
─
|
─
|
─
|
─
|
Opening time
|
[ms]
|
≤ 50
|
≤ 50
|
≤ 50
|
Arcing time
|
[ms]
|
≤ 15
|
≤ 15
|
≤ 15
|
Breaking time
|
[ms]
|
≤ 70
|
≤ 70
|
≤ 70
|
Closing operation rated voltage
|
[V]
|
AC/DC 110/220/230/48/24
|
AC/DC 110/220/230/48/24
|
AC/DC 110/220/230/48/24
|
Opening operation rated voltage
|
[V]
|
AC/DC 110/220/230/48/24
|
AC/DC 110/220/230/48/24
|
AC/DC 110/220/230/48/24
|
Charging motor rated voltage
|
[V]
|
AC/DC 110/220/230/48/24
|
AC/DC 110/220/230/48/24
|
AC/DC 110/220/230/48/24
|
Charging motor rated power
|
[W]
|
70
|
70, 120
|
70
|
70, 120
|
70
|
70, 120
|
Energy storage time
|
[s]
|
≤ 15
|
≤ 15
|
≤ 15
|
Mechanical endurance
|
[ cycles ]
|
10,000/20,000/30,000
|
20,000
|
20,000
|
Auxiliary switch
|
NO+NC
|
8NO+8NC (Max.10NO+10NC)
|
8NO+8NC (Max.10NO+10NC)
|
8NO+8NC (Max.10NO+10NC)
|
Secondary circuit power frequency withstand voltage (1min)
|
[V]
|
2,000
|
2,000
|
2,000
|
Short circuit current breaking times
|
[ cycles ]
|
274
|
274
|
274
|
Rated short time current duration
|
[s]
|
4
|
4
|
4
|
Breaker grading
|
[ms]
|
M2-E2-C2
|
M2-E2-C2
|
M2-E2-C2
|
More details please go to "Download" area to download the catalogs or contact us!
|